12 flashcards from the Definitions, General Requirements, and Plans domain. Read the front, show the answer, then grade yourself. Cards you miss come back sooner when you return to this page. No signup.

0 due today12 to learn12 cards

Flashcard · Definitions, General Requirements, and Plans

Where are NEC definitions?

Print these cards (PDF) · cut-out sheets: print double-sided, flip on the long edge

Send these free cards to a coworker.

The course has 161 cards with spaced review.It also adds every question you miss to your deck.

Terms and refunds · Secure checkout by Stripe · Billed by Nori Software

Not sure where to start? Take the free 10-question check.

All 12 cards

The same signed cards as the trainer above, in one list to read or print.

Where are NEC definitions?
Article 100, in alphabetical order. The 2023 edition gathers nearly all defined terms there.NEC 2023 Article 100
What does Article 90 cover?
The Code's purpose and scope, how it is enforced, and how to read mandatory rules, permissive rules and informational notes.NEC 2023 Article 90
Does an informational note create a requirement?
No. It explains or recommends. Only the rule text itself is enforceable.NEC 2023 Article 90
"Shall" versus "shall be permitted"?
"Shall" is mandatory. "Shall be permitted" allows something but does not require it.NEC 2023 Article 90
Continuous load: what time threshold?
Maximum current expected to continue for 3 hours or more.NEC 2023 Article 100 (continuous load)
Grounded conductor versus neutral conductor?
A grounded conductor is any conductor intentionally connected to earth. A neutral comes from the neutral point of a system. A corner-grounded delta phase is grounded but is not a neutral.NEC 2023 Article 100
Terminal temperature rule for circuits of 100 A or less?
Use the 60°C ampacity unless the equipment terminals are marked for 75°C. Above 100 A, use 75°C unless marked otherwise.NEC 2023 Article 110 (terminal temperature limits)
Interrupting rating rule?
Equipment that interrupts fault current must be rated for at least the fault current available at its line terminals.NEC 2023 Article 110 (interrupting rating)
What sets working space depth?
The nominal voltage to ground and the Condition (1, 2 or 3), which depends on what is across the space.NEC 2023 Article 110, Part II
Working space width and height?
Width at least 30 in. or the width of the equipment, whichever is more. Height at least 6½ ft.NEC 2023 Article 110, Part II
Plan scale 1/8 in. = 1 ft: how many feet per inch?
8 ft. Divide the measured inches by 0.125, or multiply by 8.Plan reading (no NEC section)
First three things to read on an electrical sheet?
The legend or symbol list, the scale, and the general notes. Then the schedules.Plan reading (no NEC section)