Flashcard · Electrical Theory and Calculations

Three-phase current from VA?

Print these cards (PDF) · cut-out sheets: print double-sided, flip on the long edge

Send these free cards to a coworker.

The course has 158 cards with spaced review.It also adds every question you miss to your deck.

Terms and refunds · Secure checkout by Stripe · Billed by Nori Software

Not sure where to start? Take the free 10-question check.

All 12 cards

The same signed cards as the trainer above, in one list to read or print.

Three-phase current from VA?
I = VA ÷ (1.732 × line-to-line volts).Electrical theory: three-phase power
Handy products: 1.732 × 208, × 240 and × 480?
360.3, 415.7 and 831.4.Electrical theory: three-phase power
kVA from kW and power factor?
kVA = kW ÷ PF. kVA is always the larger number.Electrical theory: power factor
What does raising power factor do to line current for the same kW?
Lowers it. New current = old current × old PF ÷ new PF.Electrical theory: power factor correction
Single-phase voltage drop formula (circular mil method)?
VD = 2 × K × I × L ÷ CM, with L the one-way length.Electrical theory: voltage drop
Three-phase voltage drop formula?
VD = 1.732 × K × I × L ÷ CM.Electrical theory: voltage drop
K for copper and for aluminum?
About 12.9 for copper and 21.2 for aluminum, trade approximations rather than NEC values.Electrical theory: voltage drop
Sizing a conductor for drop: which formula?
CM = 2 × K × I × L ÷ VD (single-phase) or 1.732 × K × I × L ÷ VD (three-phase), then pick the first size at or above it.Electrical theory: voltage drop; NEC 2023 Chapter 9
Where do conductor areas in circular mils come from?
The conductor properties table in Chapter 9.NEC 2023 Chapter 9
Are 3% and 5% voltage drop NEC requirements?
Not for general circuits. They are recommendations in informational notes in Articles 210 and 215.NEC 2023 Articles 210 and 215 (informational notes)
Transformer full-load current, three-phase?
I = kVA × 1,000 ÷ (1.732 × V), at the voltage of the side you want.Electrical theory: transformer current
Maximum fault current at a transformer secondary (infinite primary)?
Full-load current × 100 ÷ %Z, the same as dividing by %Z as a decimal.Electrical theory: short-circuit current