Free TX Journeyman flashcards

12 flashcards from the Electrical Services, Service Equipment, and Separately Derived Systems domain. Read the front, show the answer, then grade yourself. Cards you miss come back sooner when you return to this page. No signup.

0 due today12 to learn12 cards

Flashcard · Electrical Services, Service Equipment, and Separately Derived Systems

Load calculation article in the 2026 NEC?

Print these cards (PDF) · cut-out sheets: print double-sided, flip on the long edge

Send these free cards to a coworker.

The course has 134 cards with spaced review.It also adds every question you miss to your deck.

Terms and refunds · Secure checkout by Stripe · Billed by Nori Software

Not sure where to start? Take the free 10-question check.

All 12 cards

The same signed cards as the trainer above, in one list to read or print.

Load calculation article in the 2026 NEC?
Article 120 (it was Article 220 in earlier editions; check your 2026 index). The standard method for feeders and services is Part III.NEC 2026 Article 120
Dwelling small-appliance and laundry loads in the standard method?
1,500 VA for each small-appliance circuit (at least two) and 1,500 VA for the laundry circuit.NEC 2026 Article 120, Part III
Four or more fastened-in-place dwelling appliances?
Take 75% of their combined nameplate load (ranges, dryers, space heating and AC are figured separately).NEC 2026 Article 120, Part III (fastened-in-place appliances)
Dwelling service conductors at 120/240 V single-phase carrying the whole load?
Ampacity at least 83% of the service rating. Example: 200 A x 0.83 = 166 A.NEC 2026 310.12
Minimum service disconnect rating for a one-family dwelling?
100 A, 3-wire.NEC 2026 230.79(C)
Clearances for overhead service conductors?
230.24: above roofs, and vertical clearance above grade by what is underneath (walkways, residential driveways, streets).NEC 2026 230.24
Grounding electrode conductor size?
Table 250.66, read from the largest ungrounded service-entrance conductor (or the equivalent area of parallel sets).NEC 2026 250.66; Table 250.66
GEC that connects only to ground rods?
Not required to be larger than 6 AWG copper.NEC 2026 250.66(A)
GEC that connects only to a concrete-encased electrode?
Not required to be larger than 4 AWG copper.NEC 2026 250.66(B)
Main bonding jumper and supply-side bonding jumper size?
Table 250.102(C)(1), read from the size of the service conductors.NEC 2026 250.28; Table 250.102(C)(1)
When does a single ground rod need a supplemental electrode?
Always, unless that one rod measures 25 ohms or less to earth. Two rods are at least 6 ft apart.NEC 2026 250.53(A)
When is a metal underground water pipe a grounding electrode?
When at least 10 ft is in direct contact with the earth. It always needs a supplemental electrode.NEC 2026 250.52(A)(1); 250.53(D)