- Load calculation article in the 2026 NEC?
- Article 120 (it was Article 220 in earlier editions; check your 2026 index). The standard method for feeders and services is Part III.NEC 2026 Article 120
- Dwelling small-appliance and laundry loads in the standard method?
- 1,500 VA for each small-appliance circuit (at least two) and 1,500 VA for the laundry circuit.NEC 2026 Article 120, Part III
- Four or more fastened-in-place dwelling appliances?
- Take 75% of their combined nameplate load (ranges, dryers, space heating and AC are figured separately).NEC 2026 Article 120, Part III (fastened-in-place appliances)
- Dwelling service conductors at 120/240 V single-phase carrying the whole load?
- Ampacity at least 83% of the service rating. Example: 200 A x 0.83 = 166 A.NEC 2026 310.12
- Minimum service disconnect rating for a one-family dwelling?
- 100 A, 3-wire.NEC 2026 230.79(C)
- Clearances for overhead service conductors?
- 230.24: above roofs, and vertical clearance above grade by what is underneath (walkways, residential driveways, streets).NEC 2026 230.24
- Grounding electrode conductor size?
- Table 250.66, read from the largest ungrounded service-entrance conductor (or the equivalent area of parallel sets).NEC 2026 250.66; Table 250.66
- GEC that connects only to ground rods?
- Not required to be larger than 6 AWG copper.NEC 2026 250.66(A)
- GEC that connects only to a concrete-encased electrode?
- Not required to be larger than 4 AWG copper.NEC 2026 250.66(B)
- Main bonding jumper and supply-side bonding jumper size?
- Table 250.102(C)(1), read from the size of the service conductors.NEC 2026 250.28; Table 250.102(C)(1)
- When does a single ground rod need a supplemental electrode?
- Always, unless that one rod measures 25 ohms or less to earth. Two rods are at least 6 ft apart.NEC 2026 250.53(A)
- When is a metal underground water pipe a grounding electrode?
- When at least 10 ft is in direct contact with the earth. It always needs a supplemental electrode.NEC 2026 250.52(A)(1); 250.53(D)