Flashcard · Electrical Services, Service Equipment, and Separately Derived Systems

Where are service conductor sizing and service disconnect rules?

Print these cards (PDF) · cut-out sheets: print double-sided, flip on the long edge

Send these free cards to a coworker.

The course has 178 cards with spaced review.It also adds every question you miss to your deck.

Terms and refunds · Secure checkout by Stripe · Billed by Nori Software

Not sure where to start? Take the free 10-question check.

All 12 cards

The same signed cards as the trainer above, in one list to read or print.

Where are service conductor sizing and service disconnect rules?
Article 230, with Article 250 for grounding and bonding.Article 230
Minimum size of a one-family dwelling service disconnect?
100 A, 3-wire.NEC 2026 230.79
Maximum number of service disconnects in one enclosure group?
Six disconnects per service location, grouped together.NEC 2026 230.71
What is the standard method for a dwelling general lighting load?
3 VA per square foot of floor area, with the demand tiers applied to the subtotal.NEC 2026 Article 120
Dwelling lighting demand tiers?
First 3,000 VA at 100%, 3,001 to 120,000 VA at 35%, over 120,000 VA at 25%.NEC 2026 Article 120
Subtotal of 14,000 VA. Lighting demand?
3,000 + (11,000 x 0.35) = 6,850 VA.NEC 2026 Article 120
Small-appliance and laundry loads in a dwelling?
1,500 VA for each of two small-appliance circuits and 1,500 VA for the laundry circuit.NEC 2026 Article 120
Fastened-in-place appliance demand in a dwelling?
75% of the nameplate total when four or more are on the service or feeder, not counting ranges, dryers, heating or air conditioning.NEC 2026 Article 120
Electric dryer load in a dwelling?
5,000 VA or the nameplate rating, whichever is larger, then demand factors as the section allows.NEC 2026 Article 120
Which table sizes the grounding electrode conductor?
Table 250.66, from the size of the largest ungrounded service conductor or equivalent area.NEC 2026 250.66
Ground rod GEC need not exceed what size?
6 AWG copper when it is the sole connection to rod electrodes.NEC 2026 250.66(A)
Concrete-encased electrode GEC need not exceed what size?
4 AWG copper when it is the sole connection to that electrode.NEC 2026 250.66