Try a full lesson: Motor circuits: which current does which job

This is a complete lesson from the course (module 7 of 10, Topic K.7, C.7), followed by 10 practice questions with full explanations. Nothing to sign up for.

What this lesson covers

Motors make up a large share of the Calculations portion of the Texas master exam: 6 of the 30 scored calculation questions and 7 of the 70 scored NEC Knowledge questions are on motors and generators. The questions look different from each other, but they all rest on one idea. A motor has three different currents, and each one has its own job. Mix them up and every later step is wrong. This lesson gives you a four-step habit: table current, conductors, protection, then feeder.

We cite the 2026 NEC by section number in our own words. Keep your own copy open beside this page.

Step 1: pick the right current

CurrentWhere it comes fromWhat it is used for
Table full-load currentTable 430.248 (single-phase) or Table 430.250 (three-phase)Conductors, short-circuit and ground-fault protection, disconnect (430.6(A)(1))
Nameplate currentThe motor's nameplateOverload protection only (430.6(A))
Locked-rotor currentStarting dataNothing you size on this exam

Find the horsepower row and the voltage column in the table. A 20 hp, 460 V, three-phase motor is 27 A. A 15 hp motor is 21 A. A 3 hp motor is 4.8 A. Do not read the nameplate for anything except the overload.

Step 2: size the conductors

One motor takes 125% of the table current (430.22). Then check the termination temperature, as for any conductor.

20 hp, table current 27 A: 27 × 1.25 = 33.75 A. With 60°C terminations, 8 AWG copper (40 A) passes.

Step 3: size the protection

Three separate devices, three separate percentages.

Short-circuit and ground-fault device (430.52). A percentage of the table current, by device type: inverse-time breaker 250%, dual-element fuse 175%, nontime-delay fuse 300%, instantaneous-trip breaker 800%. If the result is not a standard rating, the next higher standard rating is allowed (the exception to 430.52(C)(1)). If the device trips when the motor starts, the exceptions allow a higher value up to a stated cap.

Overload device (430.32). A percentage of the nameplate current: 125% for a motor with a service factor of 1.15 or more or a temperature rise of 40°C or less, and 115% for other motors.

Disconnect (430.110(A)). At least 115% of the table current.

Step 4: size the feeder when there are several motors

Conductors (Article 430). 125% of the largest motor's table current, plus the table current of every other motor on the feeder.

Protection (430.62). The rating of the largest branch-circuit short-circuit device on the feeder, plus the table current of every other motor. The feeder device may not exceed that total, so you round down to a standard size.

Worked examples

Example 1: one motor. A 20 hp, 460 V, three-phase motor. Nameplate current 25.5 A, service factor 1.15. Table current 27 A.

  • Conductors: 27 × 1.25 = 33.75 A.
  • Inverse-time breaker: 27 × 2.5 = 67.5 A. That is not a standard size, so the next higher is 70 A.
  • Dual-element fuse: 27 × 1.75 = 47.25 A. The next higher standard size is 50 A.
  • Overload: 25.5 × 1.25 = 31.9 A.
  • Disconnect: 27 × 1.15 = 31.05 A or more.

Example 2: a feeder. The feeder supplies the 20 hp motor above (27 A, 70 A breaker), a 15 hp motor (21 A) and a 3 hp motor (4.8 A), all 460 V, three-phase.

  • Conductors: 27 × 1.25 = 33.75, plus 21, plus 4.8 = 59.55 A. 6 AWG copper at 75°C is 65 A, which meets it.
  • Protection: 70 + 21 + 4.8 = 95.8 A. The feeder device may not exceed this, so choose 90 A, the largest standard size at or below it.

Common traps

  • Table or nameplate. Overload is the only step that uses the nameplate. If you used 25.5 A for the breaker, you used the wrong current.
  • 125% on the largest motor only. On a feeder, the other motors go in at 100%.
  • Round up on the branch, down on the feeder. The branch-circuit device may go to the next higher standard size. The feeder device may not exceed the calculated value.
  • Voltage column. A 208 V motor reads the 208 V column. Reading the 230 V column gives a wrong current.
  • Exceptions only when asked. The higher starting percentages apply only when the question says the first value will not carry the start.

Check yourself

Try the ten questions in the free practice set for this lesson. The same four-step habit works on each one.

Where to look in the NEC

  • Table 430.248, Table 430.250 and 430.6(A)
  • 430.22 and Article 430 for conductors
  • 430.52 and its table for short-circuit and ground-fault protection; 430.32 for overload
  • 430.62 for feeder protection; 430.110(A) for the disconnect
  • Table 310.16 and 240.6(A); Article 445 and 445.13 for generators

Practice set

Print these questions for a class (PDF) Answer key on page 2. Free, no signup.

Pick an answer, then check it. Every wrong option is explained too.

1. Motors and Generators

Which NEC table gives the full-load current to use when you size the conductors for a three-phase induction motor?

2. Motors and Generators

Which current is used to set a motor's overload protection?

3. Motors and Generators

A 7.5 hp, 230 V, three-phase motor has a table full-load current of 22 A. What is the minimum ampacity of its branch-circuit conductors?

4. Motors and Generators

For the same motor with a table full-load current of 22 A, what is the largest standard inverse-time circuit breaker permitted for branch-circuit short-circuit and ground-fault protection, using the general percentage and the next higher standard size where the result is not a standard rating?

5. Motors and Generators

A motor has a nameplate full-load current of 18.6 A and a service factor of 1.15. What is the maximum overload setting before any starting exception is used?

6. Motors and Generators

A motor disconnecting means is rated in amperes. What is its minimum rating compared with the motor's full-load current?

7. Motors and Generators

A feeder supplies a 10 hp motor with a table full-load current of 14 A and a 5 hp motor with a table full-load current of 7.6 A, both 460 V, three-phase. What is the minimum ampacity of the feeder conductors?

8. Motors and Generators

The conductors from a generator's terminals to its first overcurrent device must have an ampacity of at least what percent of the generator nameplate current?

9. Motors and Generators

A legally required standby system must supply its loads within how many seconds after normal power fails?

10. Motors and Generators

What is the full-load current of a 50 kVA, 208 V, three-phase generator?

0 of 10 checkedCheck each answer to see your score.

Practice this module in the course: Motors and generators

Studying with a coworker? Send them this free lesson.

Free TX Master study plan

A week-by-week plan from today to your exam, weighted to the published exam outline. We show it here and email you a copy.

The TX Master course

Available now · instant access

Ready for the rest? The full course

  • 10modules of lessonsEvery task on the outline
  • 1timed practice exams72 questions in 232 minutes
  • 168practice questionsEach one explained
  • 1week-by-week study planSet to your exam date

Turn a practice answer into a study step. In untimed practice, ask Lug AI about any question you answer, follow up, then see your weakest topics and what to drill next.

See all 10 modules
  1. Definitions, theory and plan reading
  2. Services, grounding and transformers
  3. Feeders
  4. Branch circuits and conductor sizing
  5. Wiring methods and materials
  6. Equipment and devices
  7. Motors and generators
  8. Controls and disconnecting means
  9. Special occupancies, equipment and conditions
  10. Solar PV and EV charging
Texas Master course$149Get the texas Master course · $149

Instant access. Terms and refunds · Secure checkout by Stripe · Billed by Nori Software

    Compare plans

    Every answer comes with a full explanation.

    Questions are original and written to TDLR's published content outline. Code is cited by section number so you can look it up in your own copy. Think something is wrong? Report it.