Transformer Calculations: kVA to Amps for Electricians
Transformer problems on the Texas journeyman Calculations portion start the same way every time: turn kVA into amps on each side. Once you have the two currents, the rest of the problem is a lookup you already know how to do. The conversion is short, and the mistakes are all in the order of the steps, so this post fixes the order.
Why transformers are on the exam
The services, service equipment and separately derived systems area carries 10 scored items across both portions, 4 of them on Calculations, and the PSI Candidate Information Bulletin (updated 9/15/2026) lists transformers within it. A transformer feeding a panel is a separately derived system, and the NEC's overcurrent protection rules for transformers are in Article 450. We cite by number only, so find the sections in your own 2026 book and read the conditions there.
Check where you stand on TX Journeyman
Scored by domain, untimed. No signup.
Start the free 10-question checkThe two formulas
A transformer's rating is in kilovolt-amperes (kVA), and one kVA is 1,000 volt-amperes. To find the current on either side, divide the volt-amperes by the voltage, and for three-phase also by 1.732, the square root of 3.
- Single-phase current = (kVA × 1,000) ÷ voltage
- Three-phase current = (kVA × 1,000) ÷ (1.732 × line voltage)
Use the line voltage for the side you are working on. The primary and secondary currents are different because the voltages are different, and the power is the same on both sides, ignoring losses.
Worked example: single-phase
A 25 kVA single-phase transformer has a 480 volt primary and a 240 volt secondary.
- Primary current: 25,000 ÷ 480 = about 52.1 A
- Secondary current: 25,000 ÷ 240 = about 104.2 A
The check is that the lower-voltage side carries the larger current, here about twice, because the voltage is half.
Worked example: three-phase
A 75 kVA three-phase transformer has a 480 volt primary and a 208 volt secondary.
- Primary current: 75,000 ÷ (1.732 × 480) = 75,000 ÷ 831.4 = about 90.2 A
- Secondary current: 75,000 ÷ (1.732 × 208) = 75,000 ÷ 360.3 = about 208.2 A
If your calculator has a square-root key, enter 3 and press it. Otherwise 1.732 is close enough for exam-style rounding, but look at the options: if two choices differ by less than the effect of rounding, carry more digits.
The three steps that follow
- Convert to current on each side. As above.
- Find the overcurrent protection rule. Article 450 has rules for the primary and secondary protection of transformers, with percentages that depend on the current and the arrangement. Read the condition in your book. The percentages are not for memory.
- Round to a standard device rating. 240.6(A) lists standard ratings. Read the question to see whether it allows the next size up.
Then size conductors from the load or the device rating, with the ampacity steps in our conductor ampacity guide, and the grounding conductors from their tables in our grounding electrode conductor guide.
Mistakes to avoid
- Using phase voltage in the three-phase formula. Use the line voltage the question gives.
- Using 1.732 on a single-phase unit. It belongs only to the three-phase formula.
- Mixing primary and secondary. Label each current as you write it.
- Forgetting the 1,000. A kVA rating is thousands of volt-amperes. A figure off by 1,000 is the commonest wrong option.
- Applying exceptions. The bulletin tells you not to consider exceptions or optional methods unless a question directs you to them.
Drill it
Make ten transformers with different kVA and voltage pairs. For each, write both currents and check that power on the two sides is equal. Check each pair with the transformer calculator, which shows every step. For three-phase power with a power factor, check your arithmetic with the Ohm's law calculator. Then take a mixed set from our calculations portion guide and time the full chain, from kVA to device size.
Find your weak spot first
Transformers are one of several types inside the services area. Take the free 10-question check to see where your score sits across all ten areas. No signup, and every answer comes with an explanation.
FAQ
How do I convert kVA to amps?
Multiply kVA by 1,000 and divide by the voltage. For three-phase, also divide by 1.732.
Why is secondary current larger than primary on a step-down transformer?
Power is nearly equal on both sides, so the lower-voltage side carries more current.
Where are transformer overcurrent rules?
In Article 450. Read the specific section and conditions in your 2026 NEC.
Related guides
Free tools for this topic
Keep reading
Your next step
Ready to see where you stand on TX Journeyman?
Free, untimed and scored by domain. No signup.
Start the free 10-question checkTexas Journeyman course. Lessons, timed practice exams and a plan around your exam date. Get Texas Journeyman course · $99 See the plans or read the free sample lesson.Terms and refunds
More free practice
- Read a free lesson
- Take the free 25-question timed test
- Question of the day
- Free flashcards
- Print a class quiz (free PDF)
- Print the flashcards as cut-out cards (free PDF)
The free check and the course are on the TX Journeyman page.