NEC conduit fill: Chapter 9 tables and Annex C

Conduit fill questions send you into the back of the book. They are quick once you know the three tables that carry the work. This guide shows the method with your 2026 NEC open. We cite tables by number and never reproduce their rows.

Check anything you rely on against your own licensed code book and the edition your AHJ enforces.

Where to turn

  • Chapter 9, Table 1 gives the maximum percent of a raceway's cross section that conductors may fill, by number of conductors. Read the notes to the tables with it.
  • Chapter 9, Table 4 gives raceway dimensions by type and trade size, including the area at each fill percentage. Pick the table for your raceway: EMT, rigid metal, PVC and others each have one.
  • Chapter 9, Table 5 gives the area of each insulated conductor by type and size. Table 8 covers bare conductors.
  • Annex C has ready-made tables of the maximum number of same-size conductors for a given raceway. It is informational, but the Chapter 9 notes point to it, so mark it too.

Check where you stand on TX Journeyman

Scored by domain, untimed. No signup.

Start the free 10-question check

The method

  1. Choose the raceway type and the conductor insulation type.
  2. From Table 5, take each conductor's area and add them. Count insulated equipment grounding conductors too.
  3. Use Table 1 to find the fill percentage for the number of conductors. Table 1 gives 53% for one conductor, 31% for two and 40% for more than two.
  4. In the Table 4 section for your raceway, find the smallest trade size whose area at that percentage is at least the total.
  5. If all conductors are the same size and type, check Annex C to confirm your answer.

Ask Lug before you buy AI your Bonding Jumper study buddy

See what's on the TX Journeyman exam, test yourself with 5 quick questions, or find the plan that fits you.

The TX Journeyman course

Available now · instant access

Learn the subject areas the exam tests most, then prove it on timed practice exams in the two-portion format.

  • 10modules of lessonsEvery task on the outline
  • 3full-length timed exams80 questions in 240 minutes each
  • 411practice questionsEach one explained
  • 1week-by-week study planSet to your exam date

Turn a practice answer into a study step. In untimed practice, ask Lug AI about any question you answer, follow up, then see your weakest topics and what to drill next.

Texas Journeyman course$99Get the course · $99

Instant access. Terms and refunds · Secure checkout by Stripe · Billed by Nori Software

Compare plans

Every answer comes with a full explanation.

Worked example

A run of EMT longer than 24 inches carries four 6 AWG THHN, two 8 AWG THHN and one 10 AWG THHN equipment grounding conductor.

  • Table 5 areas, square inches: 6 AWG is 0.0507 each, 8 AWG is 0.0366 each, 10 AWG is 0.0211.
  • Total: 4 × 0.0507 = 0.2028, plus 2 × 0.0366 = 0.0732, plus 0.0211. The sum is 0.2971 square inches.
  • Seven conductors means the over-two percentage, 40%.
  • Table 4 for EMT: 3/4 inch allows 0.213 square inches at 40%, which is too small. 1 inch allows 0.346, which is enough.
  • Answer: 1-inch EMT.

The mixed sizes mean Annex C is no help here, since it only covers one size at a time. That is why you need Table 5.

Common traps

  • Using the wrong table for the raceway. Table 4 has a separate section for each raceway type, and the areas differ.
  • Applying the 40% to everything. One conductor and two conductors use other percentages, so count first.
  • Forgetting grounding conductors. An insulated equipment grounding conductor is included in fill. Take its area from Table 5. A bare one uses Table 8.
  • Short nipples. The notes to the tables give different treatment for runs of 24 inches or less. Read the note, then apply it.
  • Using Annex C for mixed sizes. It lists same-size cases only.
  • Reading the wrong insulation row. THHN, THWN and XHHW have different areas. Match the type in the problem.
  • Conduit fill versus derating. Fitting the conductors does not mean the ampacity is unchanged. Adjustment for more than three current-carrying conductors is a separate step in 310.15 (2023 numbering).

Working it with the book open

Tab the Table 1 page, the Table 4 page for each raceway type you expect, and Table 5. Write each conductor's area on scratch paper, add the column once and compare with the Table 4 column for the right percentage. Put a finger on the percentage column before you read across, because the neighboring columns hold other fill percentages and are easy to misread. Recheck the count of conductors before you pick the percentage.

How to practice

Invent a dozen conductor sets, some with a ground and some with different sizes. Work each through Tables 5, 1 and 4, then check the same-size ones against Annex C. Aim for about two minutes each.

Related guides: conductor ampacity and box fill.

Start with the free 10-question check

See whether this topic is a weak spot. Take the free 10-question check. It needs no signup and explains every answer. When you want the full method worked topic by topic, the Bonding Jumper course comes second.

Not affiliated with or endorsed by TDLR, PSI or NFPA. NEC and National Electrical Code are registered trademarks of NFPA.

Sources

Show the list

Facts checked 24 October 2026 against the sources listed above. If something has changed, tell us and we will correct it within 2 business days.

Your next step

Ready to see where you stand on TX Journeyman?

Free, untimed and scored by domain. No signup.

Start the free 10-question check

Texas Journeyman course. Lessons, timed practice exams and a plan around your exam date. Get Texas Journeyman course · $99 See the plans or read the free sample lesson.Terms and refunds

Want a timed run? Try the free 25-question mini-mock. The first 5 need no email.

Free tools for this topic

Prefer paper? Free printables

From the blog