The formulas
Power factor is true power over apparent power, and it is the cosine of the angle φ between voltage and current. The three powers form a right triangle: kW along the base, kVAR up the side and kVA on the slope. A capacitor in parallel with the load supplies reactive power that cancels part of the load's, which shortens the kVAR side and with it the kVA, while the kW stays the same.
- Capacitor kVAR = kW × (tan φ1 − tan φ2), where φ1 = acos(present PF) and φ2 = acos(target PF).
- kVA = kW ÷ PF.
- Line current, single-phase: I = kW × 1,000 ÷ (V × PF). Three-phase: I = kW × 1,000 ÷ (1.732 × V × PF), with V line to line.
- Current cut = 1 − PF1 ÷ PF2. The same kW at a higher power factor needs less current.
- Capacitance: C = Q ÷ (2π f V²), with Q in VAR across the capacitor. A delta bank puts one capacitor across each pair of lines, so each takes Q ÷ 3 at the line voltage.
Worked example 1: 100 kW three-phase, 0.70 to 0.95
480 V, 60 Hz. tan(acos 0.70) = 1.0202 and tan(acos 0.95) = 0.3287. Capacitor kVAR = 100 × (1.0202 − 0.3287) = 69.15 kVAR. kVA falls from 100 ÷ 0.70 = 142.9 to 100 ÷ 0.95 = 105.3. Current falls from 100,000 ÷ (1.732 × 480 × 0.70) = 171.8 A to 100,000 ÷ (1.732 × 480 × 0.95) = 126.6 A, a 26.3% cut. Each capacitor of a delta bank supplies 69.15 ÷ 3 = 23.05 kVAR at 480 V, so C = 23,051 ÷ (2π × 60 × 480²) = 265.4 µF per phase.
Worked example 2: 8 kW single-phase, 0.8 to 1.0
240 V, 60 Hz. tan(acos 0.8) = 0.75 and tan(acos 1.0) = 0, so the capacitor supplies 8 × 0.75 = 6.0 kVAR. kVA falls from 10 to 8 and current from 41.7 A to 33.3 A, a 20% cut. C = 6,000 ÷ (2π × 60 × 240²) = 276.3 µF. This is the load from the power factor guide, worked the other way.
These are original arithmetic examples, not exam questions.
Where it fits
The apparent vs true power guide sets out the power triangle these steps stand on. For the power formulas on their own, single-phase and three-phase, use the Ohm's law calculator, and for kVA to amps on each side of a transformer, the transformer calculator.
What this calculator leaves out
- Wye-connected banks: each capacitor sits at the line voltage ÷ 1.732, so it needs three times the delta value in µF for the same kVAR.
- Standard bank sizes: round to a rating the maker offers at your system voltage.
- Harmonics, switched or automatic banks, and capacitors placed at individual motors.
- Conductor and overcurrent sizing for the bank, which come from the NEC.
Power factor correction questions
What is kVAR in power factor correction?
kVAR is kilovolt-amperes reactive, the power that flows back and forth between the source and an inductive load each cycle without doing work. A load's kVAR is its kW times tan(acos PF). A capacitor supplies kVAR of the opposite sign, so the capacitor kVAR you need is kW × (tan φ1 − tan φ2). For 100 kW at 0.70 that is 102.02 kVAR now and 32.87 kVAR at 0.95, so the capacitor supplies 69.15 kVAR.
Why does correcting power factor cut the current?
The load still uses the same kW, but at a higher power factor it needs fewer kVA to get it, and the current follows the kVA. Current falls in the ratio PF1 ÷ PF2. Going from 0.70 to 0.95 cuts it by 1 − 0.70 ÷ 0.95 = 26.3%: on a 100 kW, 480 V three-phase load, from 171.8 A to 126.6 A. The capacitor supplies the reactive current locally, so it no longer travels back to the source.
How do I size a power factor correction capacitor in µF?
Use C = Q ÷ (2π f V²), with Q in VAR and V in volts across the capacitor. On single-phase, Q is the whole kVAR. A three-phase delta bank has one capacitor across each pair of lines, so each takes one third of the kVAR at the line voltage. For 69.15 kVAR at 480 V and 60 Hz: 23,051 VAR ÷ (2π × 60 × 480²) = 265.4 µF per phase.
Why aim for 0.95 and not 1.0?
It is a design choice, not a code rule. The last step costs the most: taking 100 kW from 0.95 to 1.0 needs another 32.87 kVAR, about 48% more capacitor than the 69.15 kVAR that got it to 0.95, for 6.3 A less current at 480 V. A fixed bank sized for 1.0 at full load also overshoots when the load drops, because the capacitor keeps supplying the same kVAR while the motors need less, and the circuit turns capacitive. Stopping short of 1.0 takes most of the current cut and leaves margin against that.