Power Factor Correction Formula: 3 Worked Examples

The power factor correction formula is capacitor kVAR = kW × (tan(acos PF1) minus tan(acos PF2)), where PF1 is the power factor you have and PF2 is the one you want. The kW does not change. Everything else follows from it: the kVA, the line current and the size of the capacitor in microfarads. This post works the formula through three examples, single-phase, three-phase and a delta capacitor bank, with every step written out.

The power triangle in words

Picture a right triangle. The flat base is true power in kW, the work the load does. The upright side is reactive power in kVAR, the energy a motor's magnetic field borrows and hands back each cycle. The sloping side is apparent power in kVA, what the conductors and transformer actually carry. The angle at the base is the phase angle between voltage and current, and the power factor is its cosine, which is the base divided by the slope.

Two facts make correction work. Inductive loads lag and capacitors lead, so a capacitor in parallel supplies reactive power that cancels part of the load's. And because the capacitor does no work, the base of the triangle stays put while the upright side shrinks. The slope gets shorter, so the kVA and the current fall. Our apparent vs true power guide draws the same triangle with an 8, 6 and 10 example.

The formulas

  • Reactive power of a load: kVAR = kW × tan(acos PF). The tan(acos PF) factor is the kVAR per kW at that power factor.
  • Capacitor kVAR needed: kW × (tan(acos PF1) minus tan(acos PF2)).
  • Apparent power: kVA = kW ÷ PF.
  • Line current, single-phase: amps = kW × 1,000 ÷ (volts × PF).
  • Line current, three-phase: amps = kW × 1,000 ÷ (1.732 × line volts × PF). The 1.732 is the square root of 3.
  • Capacitance: microfarads = VAR ÷ (2π × frequency × volts²) × 1,000,000, using the voltage across the capacitor.

If you would rather not take arc cosines, find the sine side first: tan(acos PF) = √(1 minus PF²) ÷ PF. At 0.8 that is 0.6 ÷ 0.8 = 0.75.

Example 1: single-phase, 8 kW from 0.8 to 1.0

A single-phase 240 volt load uses 8 kW at a power factor of 0.8. How much capacitor brings it to 1.0?

  1. Load kVAR now: tan(acos 0.8) = 0.75, so 8 × 0.75 = 6.0 kVAR.
  2. Load kVAR at 1.0: tan(acos 1.0) = 0, so 0 kVAR.
  3. Capacitor kVAR: 6.0 minus 0 = 6.0 kVAR.
  4. kVA before and after: 8 ÷ 0.8 = 10 kVA, then 8 ÷ 1.0 = 8 kVA.
  5. Current before and after: 8,000 ÷ (240 × 0.8) = 41.7 A, then 8,000 ÷ 240 = 33.3 A.

The same 8 kW of work now takes 8.3 A less, a 20% cut. At 60 Hz the capacitor is 6,000 ÷ (2π × 60 × 240²) = about 276.3 µF. This is the load in our power factor guide, carried one step further to the capacitor.

Try one question

Question 1 of the free 10-question check on TX Journeyman. No signup. About 14 minutes. Most checks include 2 calculation questions, with a calculator on the page. Your progress saves in this browser for 24 hours, so you can stop and finish later. Then ask Lug, the AI study assistant, why the answer is right and the others are wrong.

Question 1 of 10 · free checkUntimed

Special Occupancies, Equipment, and Conditions

After normal power fails, within how many seconds must an emergency system make power available to its required loads?

Press A-D or 1-4 to choose an answer while this question is on screen.

Choose an answer to begin

Example 2: three-phase, 100 kW from 0.70 to 0.95 at 480 V

A 480 volt three-phase motor load uses 100 kW at a power factor of 0.70. The target is 0.95. Find the capacitor kVAR and the line current before and after.

  1. tan(acos 0.70): √(1 minus 0.49) ÷ 0.70 = 0.71414 ÷ 0.70 = 1.02020.
  2. tan(acos 0.95): √(1 minus 0.9025) ÷ 0.95 = 0.31225 ÷ 0.95 = 0.32868.
  3. Capacitor kVAR: 100 × (1.02020 minus 0.32868) = 100 × 0.69152 = 69.15 kVAR. The load had 102.02 kVAR and keeps 32.87 kVAR.
  4. kVA before and after: 100 ÷ 0.70 = 142.9 kVA, then 100 ÷ 0.95 = 105.3 kVA.
  5. Current before: 100,000 ÷ (1.732 × 480 × 0.70) = 171.8 A.
  6. Current after: 100,000 ÷ (1.732 × 480 × 0.95) = 126.6 A.

The current falls in the ratio of the power factors: 1 minus 0.70 ÷ 0.95 = 26.3% less, for the same 100 kW. That freed capacity is the point of correcting, because conductors and transformers heat by current, not by work done.

Example 3: microfarads per phase for a delta bank

Use the 69.15 kVAR from Example 2. A three-phase delta bank has one capacitor across each pair of lines, so each capacitor sees the full 480 V line voltage and supplies one third of the total.

  1. VAR per capacitor: 69,152 ÷ 3 = 23,051 VAR, or 23.05 kVAR.
  2. 2π × f × V²: 2π × 60 × 480² = 2π × 60 × 230,400 = 86,858,754.
  3. Capacitance: 23,051 ÷ 86,858,754 = 0.0002654 farads = 265.4 µF per phase.

On a single-phase load there is only one capacitor, so it takes the whole kVAR at the circuit voltage, as in Example 1. On a 50 Hz system the same kVAR needs 60 ÷ 50 = 1.2 times the capacitance.

These are study numbers. A capacitor bank on an installed system is picked from the equipment maker's data and installed under the NEC.

Mistakes to avoid

  • Using kVA where the formula wants kW. The formula multiplies true power. Put 142.9 kVA into Example 2 in place of 100 kW and you get 98.79 kVAR, about 43% more capacitor than the load needs. If a question gives volts and amps, find kVA first, then multiply by the power factor to get kW.
  • Leaving 1.732 off the three-phase current. 100,000 ÷ (480 × 0.70) gives 297.6 A, not 171.8 A. If a three-phase answer looks too big by about 1.7 times, the square root of 3 is missing.
  • Subtracting the power factors. 0.95 minus 0.70 is not a kVAR factor. Convert each power factor to tan(acos PF) first, then subtract.
  • Using 277 V across a delta capacitor. In a delta bank each capacitor sits between two lines, so use the 480 V line voltage. Because capacitance scales with 1 ÷ V², the wrong voltage throws the µF off by a factor of 3.
  • Dropping the 1,000 or the 1,000,000. kW to watts for current, and farads to microfarads at the end. An answer off by exactly 1,000 is a units slip.

Check your work

Work each example by hand first, then enter the same numbers into the free power factor correction calculator. It shows the tan values, the kVAR, the kVA and current before and after and the microfarads, step by step, so you can see exactly where your figures part ways. For the plain power formulas behind the current step, see our Ohm's law and power formulas post.

Find your weak spot first

Power factor sits under the motor, load and transformer calculations on the Texas journeyman exam. Take the free 10-question check to see where your score sits across all ten subject areas. No signup, and every answer comes with an explanation.

FAQ

What is the formula for power factor correction?

Capacitor kVAR = kW × (tan(acos PF1) minus tan(acos PF2)). For 100 kW going from 0.70 to 0.95, that is 100 × (1.02020 minus 0.32868) = 69.15 kVAR.

How do you do a power factor correction calculation for three-phase?

The kVAR formula is the same. The three-phase part is the current, which divides by 1.732 × line volts × PF, and the capacitance, where a delta bank splits the kVAR three ways at the line voltage.

Why does the current drop when the kW stays the same?

The capacitor supplies the reactive power locally, so the source delivers less kVA for the same kW. Current follows kVA, so it falls in the ratio PF1 ÷ PF2.

Sources

  • Calculating Power Factor, Tony R. Kuphaldt, Lessons in Electric Circuits, Vol. II, chapter 11 (All About Circuits textbook): power factor as true over apparent power and the cosine of the phase angle, and a parallel capacitor canceling an inductive load's reactive power while true power stays the same. Checked 22 Nov 2026.
  • Practical Power Factor Correction, same text, chapter 11: reactive power from true and apparent power, sizing the parallel capacitor from that kVAR and the source voltage, and the drop in apparent power and source current. Checked 22 Nov 2026.
  • Three-Phase Y and Delta Configurations, same text, chapter 10: in a delta each element sits across a pair of lines at the line voltage, and in a balanced wye the line voltage is the phase voltage times the square root of 3. Checked 22 Nov 2026.

Bonding Jumper editorial team

Free tools for this topic

Keep reading

Your next step

Ready to see where you stand on TX Journeyman?

Free, untimed and scored by domain. No signup. About 14 minutes. Most checks include 2 calculation questions, with a calculator on the page. Your progress saves in this browser for 24 hours, so you can stop and finish later.

Free 10-question check

Texas Journeyman course. Lessons, timed practice exams and a plan around your exam date.

Get Texas Journeyman course · $99

More free practice

The free check and the course are on the TX Journeyman page.

Ask Lug for a plan built around your exam date

Email me the TX Journeyman exam-day checklist

What to bring, arriving and the testing room, from the exam body's own candidate guide. It opens here and goes to your inbox.