Electrician exam formulas, with worked math

Journeyman and master electrician exams lean on a short list of formulas: Ohm's law and power, voltage drop, transformer full-load current, power factor and kVAR, and series and parallel resistance, plus the conduit offset math you use on the job. The formulas are math, not code, so you carry them in your head. The code values they feed, such as circular mils, motor currents and ampacities, come from the NEC tables in the book you bring. Each section below gives the formula, one worked example with invented numbers and the free tool that checks your answer.

Ohm's law and power, single and three phase

  • Voltage = current × resistance (V = I × R).
  • Power = voltage × current (P = V × I), with P = I² × R and P = V² ÷ R when you know resistance.
  • Three-phase apparent power = 1.732 × line volts × line amps. Real power multiplies that by the power factor.

Single-phase example. A 5,760-watt heater runs on 240 volts. Current is 5,760 ÷ 240 = 24 amperes. Resistance is 240 ÷ 24 = 10 ohms. Check it with I² × R: 24 × 24 × 10 = 5,760 watts.

Three-phase example. A 480-volt, three-phase load draws 40 amperes at a power factor of 0.85. Apparent power is 1.732 × 480 × 40 = about 33,250 volt-amperes, or 33.3 kVA. Real power is that times 0.85, about 28.3 kW. Using 3 instead of 1.732, or leaving out the power factor, gives the wrong options an exam writer offers.

Work any two values into the rest with the Ohm's law calculator, which also does three-phase power. The Ohm's law and power formulas post has more examples.

Voltage drop: 2KIL/CM and 1.732KIL/CM

  • Single-phase: drop = 2 × K × I × L ÷ CM.
  • Three-phase: drop = 1.732 × K × I × L ÷ CM.
  • K is about 12.9 for copper and 21.2 for aluminum, in ohm-circular mils per foot. I is the load current, L is the one-way length in feet and CM is the conductor's area in circular mils from Chapter 9, Table 8.
  • Percent drop = drop ÷ source volts × 100.

Single-phase example. A 240-volt circuit carries 32 amperes to a load 150 feet away on 8 AWG copper, which is 16,510 circular mils. Drop = 2 × 12.9 × 32 × 150 ÷ 16,510 = 7.50 volts, and 7.50 ÷ 240 = 3.1%. Moving up to 6 AWG brings it to 4.72 volts, or 2.0%.

Three-phase example. A 480-volt feeder carries 200 amperes 400 feet on 250 kcmil copper, which is 250,000 circular mils by definition. Drop = 1.732 × 12.9 × 200 × 400 ÷ 250,000 = 7.15 volts, and 7.15 ÷ 480 = 1.5%.

The 3% and 5% figures live in informational notes under 210.19(A) and 215.2(A) (2023 numbering). They are recommendations, not requirements, and the NEC voltage drop guide covers that trap. Check a run with the voltage drop calculator, which shows every step and finds the smallest size that meets a target percent.

Try one question

Question 1 of the free 10-question check on Master. No signup. About 15 minutes. Most checks include 2 calculation questions, with a calculator on the page. Your progress saves in this browser for 24 hours, so you can stop and finish later. Then ask Lug, the AI study assistant, why the answer is right and the others are wrong.

Question 1 of 10 · free checkUntimed

Grounding and Bonding

A service with 350 kcmil copper conductors has a GEC that runs only to two driven ground rods. Table 250.66 would give 2 AWG copper for these service conductors. What is the largest GEC the rods require?

Press A-D or 1-4 to choose an answer while this question is on screen.

Choose an answer to begin

Transformer full-load current from kVA

  • Single-phase: amperes = kVA × 1,000 ÷ volts.
  • Three-phase: amperes = kVA × 1,000 ÷ (1.732 × line volts).

Example. A 112.5 kVA three-phase transformer has a 480-volt primary and a 208Y/120-volt secondary.

  • Primary: 112,500 ÷ (1.732 × 480) = 112,500 ÷ 831.4 = about 135.3 amperes.
  • Secondary: 112,500 ÷ (1.732 × 208) = 112,500 ÷ 360.3 = about 312.3 amperes.

The same kVA flows on both sides, so the lower-voltage side carries more current. For a single-phase check, a 75 kVA transformer at 240 volts carries 75,000 ÷ 240 = 312.5 amperes. Size the conductors from the ampacity tables and the protection from Article 450. The transformer kVA guide explains why the rating is in kVA, and the transformer calculator gives the current on each side and the turns ratio.

Power factor and kVAR correction

  • Power factor = watts ÷ volt-amperes, which is the cosine of the angle between voltage and current.
  • kVA = kW ÷ power factor, and kVAR = kW × tan θ.
  • Capacitor kVAR to correct = kW × (tan θ before − tan θ after).

Example. A 60 kW three-phase load on 480 volts runs at a power factor of 0.78, and the target is 0.95.

  • tan θ at 0.78 is 0.802, and at 0.95 it is 0.329.
  • Capacitor kVAR = 60 × (0.802 − 0.329) = about 28.4 kVAR.
  • kVA falls from 60 ÷ 0.78 = 76.9 to 60 ÷ 0.95 = 63.2.
  • Line current falls from 60,000 ÷ (1.732 × 480 × 0.78) = 92.5 amperes to 76.0 amperes, a cut of about 18%, while the load does the same work.

The power factor guide covers what lowers it and why it raises current. The power factor correction calculator works the kVAR, the current before and after and the capacitor size.

Series and parallel resistance

  • Series: total = R1 + R2 + R3, and the same current flows through each.
  • Parallel: total = 1 ÷ (1/R1 + 1/R2 + 1/R3), and each branch sees the same voltage. For two resistors, product over sum.

Example. A 120-volt source feeds an 8-ohm resistor in series with a bank of 12 ohms and 24 ohms in parallel.

  • Bank: 12 × 24 ÷ (12 + 24) = 288 ÷ 36 = 8 ohms.
  • Total: 8 + 8 = 16 ohms, so current is 120 ÷ 16 = 7.5 amperes.
  • The series resistor drops 7.5 × 8 = 60 volts, leaving 60 volts across the bank.
  • Branch currents are 60 ÷ 12 = 5 amperes and 60 ÷ 24 = 2.5 amperes, which add back to 7.5.

The series vs parallel circuits guide sets out the rules side by side, and the series and parallel resistance calculator shows every step for any combination.

Ask Lug: Am I ready?

Ask Lug before you buy AI your AI study assistant

See what's on the Master exam, test yourself with 5 quick questions, or find the plan that fits you.

The Master course

Available now · instant access

Learn the load calculations, service and feeder sizing and design rules master exams lean on, then prove it on timed 100-question practice exams.

Master course$149Get the Master course · $149

Instant access. Terms and refunds · Secure checkout by Stripe · Billed by Nori Software

What's inside
  • 12modules of lessonsEvery task on the outline
  • 2timed practice exams100 questions in 240 minutes, full length at our estimate
  • 292practice questionsEach one explained
  • 1week-by-week study planSet to your exam date

Turn a practice answer into a study step. In untimed practice, ask Lug AI about any question you answer, follow up, then see your weakest topics and what to drill next.

Every answer comes with a full explanation.

Conduit offset multiplier and shrink

  • Distance between bend marks = offset depth × multiplier, where the multiplier is 1 ÷ sin θ.
  • Shrink, the run the offset uses up, = offset depth × tan(θ ÷ 2).
  • An offset is two bends, so it uses 2 × θ of the 360° allowed between pull points.

Example. An 8-inch offset.

  • At 45°: marks 8 × 1.414 = 11.31 inches apart, about 11 5/16 in. Shrink 8 × 0.414 = 3.31 inches, about 3 5/16 in. It uses 90°.
  • At 30°: marks 8 × 2 = 16 inches apart. Shrink 8 × 0.268 = 2.14 inches, about 2 1/8 in. It uses 60°.

The shallower bend takes more length but less shrink and fewer degrees. The conduit offset multiplier chart lists every common angle, and the conduit bending calculator works offsets, saddles and a running total of degrees.

Working formulas with the book open

Write the formula first, then the numbers with their units, then the answer. Most wrong options are the right formula with one slip: 120 volts for 240, 3 for 1.732, round-trip length for one-way. When a problem mixes theory and code, work the theory, carry the result forward and turn to the table it needs. Circular mils come from Chapter 9, Table 8. Motor full-load current comes from Tables 430.248 and 430.250, which 430.6(A)(1) says to use instead of the nameplate for most sizing, as the motor calculations guide shows. Numbers here are 2023 numbering, so confirm each one in the edition your exam uses. Master candidates can see how these fit the rest of the exam in the master electrician exam guide.

Take the free 10-question check

Take the free 10-question check. It is written to the 2023 NEC, needs no signup, explains every answer and names your weakest area.

FAQ

Which K should I use for voltage drop?

Use the K the question gives. If it gives none, about 12.9 for copper and 21.2 for aluminum, in ohm-circular mils per foot, are the usual figures and the defaults our voltage drop calculator uses.

Why does three-phase use 1.732?

It is the square root of 3. In a balanced three-phase system it converts line voltage and line current into the total power of all three phases, and it replaces the 2 in the single-phase voltage drop formula.

Does the NEC require a 3% voltage drop limit?

Not for ordinary branch circuits and feeders. The 3% and 5% figures sit in informational notes, which recommend but do not make a rule. Read whether a question asks what is required or what is recommended.

Not affiliated with or endorsed by NFPA, PSI or Prov, or any state licensing board. NEC and National Electrical Code are registered trademarks of NFPA.

Sources

Show the list

Bonding Jumper editorial team

Facts come from the sources listed above. If something has changed, tell us and we will correct it.

Your next step

Ready to see where you stand on Master?

Free, untimed and scored by domain. No signup. About 15 minutes. Most checks include 2 calculation questions, with a calculator on the page. Your progress saves in this browser for 24 hours, so you can stop and finish later.

Free 10-question check

Master course. Lessons, timed practice exams and a plan around your exam date.

Get Master course · $149

Want a timed run? Take the free 25-question practice test (about 30 minutes). No email needed.

Prefer paper? Free printables

All 36 related guides