Transformer kVA: what it means for the Texas exam

A transformer's kVA rating is the most apparent power, in thousands of volt-amperes, it can deliver continuously without overheating. It is rated in kVA rather than kilowatts because its heating depends on the current and voltage it carries, not on the load's power factor. The rating, together with the voltage on each side, fixes the full-load current on each side.

A transformer drawn as two coils around a core, primary on the left marked 480 volts and 54 amperes, secondary on the right marked 208Y/120 volts and 125 amperes, with the nameplate 45 kVA in the middle and the note same kVA, different current
Same kVA in and out. Lower voltage means higher current.
Use this diagram

Why kVA and not kW

The windings heat according to the current through them, and the core according to the voltage across it. Neither cares whether the current is in step with the voltage. A transformer feeding motors at a power factor of 0.8 heats just as much at its rated kVA as one feeding heaters at 1.0, even though the motors get fewer kilowatts. See apparent vs true power.

Check where you stand on TX Journeyman

Scored by domain, untimed. No signup.

Start the free 10-question check

Current on each side

Ignoring losses, the kVA is the same on both sides, so the current changes inversely with voltage.

  • Single-phase: amperes = kVA × 1,000 ÷ volts.
  • Three-phase: amperes = kVA × 1,000 ÷ (1.732 × line volts).

A worked example with invented numbers: a 45 kVA three-phase transformer, 480 volts delta primary, 208Y/120 volts secondary.

  • Primary: 45,000 ÷ (1.732 × 480) = 45,000 ÷ 831.4 = about 54.1 amperes.
  • Secondary: 45,000 ÷ (1.732 × 208) = 45,000 ÷ 360.3 = about 124.9 amperes.

The winding voltages are 480 on the delta side and 120 on the wye side, so the turns ratio of each winding pair is 4 to 1, even though the line voltages are 480 and 208. How the windings are connected is covered in wye vs delta.

Ask Lug before you buy AI your Bonding Jumper study buddy

See what's on the TX Journeyman exam, test yourself with 5 quick questions, or find the plan that fits you.

The TX Journeyman course

Available now · instant access

Learn the subject areas the exam tests most, then prove it on timed practice exams in the two-portion format.

  • 10modules of lessonsEvery task on the outline
  • 3full-length timed exams80 questions in 240 minutes each
  • 411practice questionsEach one explained
  • 1week-by-week study planSet to your exam date

Turn a practice answer into a study step. In untimed practice, ask Lug AI about any question you answer, follow up, then see your weakest topics and what to drill next.

Texas Journeyman course$99Get the course · $99

Instant access. Terms and refunds · Secure checkout by Stripe · Billed by Nori Software

Compare plans

Every answer comes with a full explanation.

Sizing a transformer

Add the load in volt-amperes, allow for any continuous loads and future growth, and pick the next standard kVA size at or above it. Running a transformer above its kVA rating for long periods shortens its insulation life. Overcurrent protection for transformers has its own rules in Article 450, and a transformer feeding a building system is a separately derived system with its own bonding and grounding.

Common mix-ups

  • Using kW for the rating. Use kVA, and convert only if the question gives power factor and asks for kW.
  • Using phase voltage in the three-phase formula. Use line-to-line voltage with 1.732.
  • Expecting the same current on both sides. The lower-voltage side carries more current.
  • Using 1.732 on a single-phase transformer.

On the Texas journeyman exam

Transformers sit in the services, service equipment and separately derived systems area, 10 scored items across both portions under the PSI bulletin. Study to find full-load current on either side and then size the conductors or protection from it. Our blog walks through transformer calculations from kVA to amps.

Practice it

The transformer calculator gives the current on each side and the turns ratio. Every term in this set is in the electrical terms glossary.

Know the terms? Take the free 10-question check

Take the free 10-question check. It needs no signup and explains every answer, so you see whether theory, grounding or wiring methods costs you the most points. When you want the full method worked topic by topic, the Bonding Jumper course comes second.

Not affiliated with or endorsed by TDLR, PSI or NFPA. NEC and National Electrical Code are registered trademarks of NFPA.

Sources

Show the list

Facts checked 26 October 2026 against the sources listed above. If something has changed, tell us and we will correct it within 2 business days.

Your next step

Ready to see where you stand on TX Journeyman?