Main bonding jumper: what it means for the Texas exam

The main bonding jumper is the connection, in the service equipment, between the grounded conductor, usually the neutral, and the equipment grounding conductors and enclosure. It is the one point where the fault path from the building's metal parts joins the conductor that runs back to the utility transformer. It is often a green screw or strap.

Inside a service panel: a neutral bar and a separate equipment grounding bar, with a strap between them labeled main bonding jumper, the incoming neutral from the utility, and a fault arrow running from a metal box onto the grounding bar, through the jumper and back out on the neutral
One bond at the service. Fault current crosses it to get back to the transformer.
Use this diagram

Why it is needed

When a hot conductor touches a grounded metal box, current flows on the equipment grounding conductor back to the panel. To reach the source and complete the circuit, it has to cross onto the neutral, which runs back to the utility transformer. The main bonding jumper is that crossing. Without it, the fault current would have only the earth to return through, the current would be too small, and the breaker would not trip. See bonding vs grounding.

Check where you stand on TX Journeyman

Scored by domain, untimed. No signup.

Start the free 10-question check

Only once

The neutral and the equipment grounding system are joined at the service and, for a separately derived system such as a transformer, at that system by its own system bonding jumper. They are not joined again downstream. In a subpanel the neutral bar floats, isolated from the enclosure, and the equipment grounds land on a separate bar. If the two were bonded in a subpanel, normal neutral current would split onto the equipment grounding conductors, raceways and enclosures, putting current on metal people touch.

Ask Lug before you buy AI your Bonding Jumper study buddy

See what's on the TX Journeyman exam, test yourself with 5 quick questions, or find the plan that fits you.

The TX Journeyman course

Available now · instant access

Learn the subject areas the exam tests most, then prove it on timed practice exams in the two-portion format.

  • 10modules of lessonsEvery task on the outline
  • 3full-length timed exams80 questions in 240 minutes each
  • 411practice questionsEach one explained
  • 1week-by-week study planSet to your exam date

Turn a practice answer into a study step. In untimed practice, ask Lug AI about any question you answer, follow up, then see your weakest topics and what to drill next.

Texas Journeyman course$99Get the course · $99

Instant access. Terms and refunds · Secure checkout by Stripe · Billed by Nori Software

Compare plans

Every answer comes with a full explanation.

Sizing

The main bonding jumper is sized under 250.102 from the size of the service conductors, not from Table 250.122. A manufacturer's screw or strap supplied with listed service equipment is the usual form. Our grounding electrode conductor sizing guide shows how the sizing tables differ.

  • System bonding jumper. The same job at a separately derived system.
  • Equipment bonding jumper. Joins parts of the equipment grounding path, for example around a flexible fitting.
  • Supply-side bonding jumper. Bonds metal parts on the line side of the service disconnect.

Common mix-ups

  • Bonding the neutral in a subpanel. It belongs only at the service or derived system.
  • Thinking the jumper is the GEC. The grounding electrode conductor runs to the electrode; the main bonding jumper stays inside the equipment.
  • Removing the green screw at the service. That breaks the fault path.
  • Calling the neutral a ground. It is the grounded conductor and carries current every day. See neutral conductor.

On the Texas journeyman exam

The main bonding jumper sits in the services, service equipment and separately derived systems area, 10 scored items across both portions under the PSI bulletin. Study to say where the bond goes, why it is not repeated, and which section sizes it.

Practice it

Every term in this set is in the electrical terms glossary.

Know the terms? Take the free 10-question check

Take the free 10-question check. It needs no signup and explains every answer, so you see whether theory, grounding or wiring methods costs you the most points. When you want the full method worked topic by topic, the Bonding Jumper course comes second.

Not affiliated with or endorsed by TDLR, PSI or NFPA. NEC and National Electrical Code are registered trademarks of NFPA.

Sources

Show the list

Facts checked 26 October 2026 against the sources listed above. If something has changed, tell us and we will correct it within 2 business days.

Your next step

Ready to see where you stand on TX Journeyman?

Free, untimed and scored by domain. No signup.

Start the free 10-question check

Texas Journeyman course. Lessons, timed practice exams and a plan around your exam date. Get Texas Journeyman course · $99 See the plans or read the free sample lesson.Terms and refunds

Want a timed run? Try the free 25-question mini-mock. The first 5 need no email.

Prefer paper? Free printables

From the blog